A/C Name: SDP AC 18 ( 2 x 15HP )
Existing Refrigerant Gas: R22 (HCFC)
New Refrigerant Gas: Hydrocarbon Refrigerant R22-a (HC)
Location: Production – Moulding Area
SDP AC 18 (2 x 15HP)
Descriptions
Before Replacing HC Refrigerant
After Replacing HC Refrigerant
Date & Time of Recording
Start = 07-31-2009 10:33:22 End = 07-31-2009 17:51:40
Start = 08-02-2009 10:14:42 End = 08-02-2009 16:27:30
Refrigerant Weight (kg)
Sys 1 = 3.18kg
Sys 2 = 3.82kg
Sys 1 = 1.4kg
Sys 2 = 1.48kg
A/C Temperature Set Point (oC)
N/A
N/A
Outdoor Temperature (oC) while start recording
32
32
Air Outlet Temp (Off-Coil)
22.1
19.6
Low Side Pressure (PSI)
Sys 1 = 55 PSI
Sys 2 = 52 PSI
Sys 1 = 55 PSI
Sys 2 = 56 PSI
High Side Pressure (PSI)
Sys 1 = 200 PSI
Sys 2 = 210 PSI
Sys 1 = 190 PSI
Sys 2 = 200 PSI
Average hourly Power Consumption (kW)
21.61
14.97
Power Saved (kW)
6.64
Operating Hour (Hour(s))
24
24
Operating day
26
26
Savings achievement
(21.61 – 14.97)/ 21.61 *100 30.7%
Monthly Savings (kWh)
6.64 x 24 x 26 = 4,143.36kWh
Energy Savings Verification
BEFORE Conversion ( refer to excel file named: SDP-AC 18 R22 )
Recording Time: Start = 07-31-2009 10:33:22, End = 07-02-2009 17:51:40 (6 Sec Interval)
Average Power (P1): 21.61 kW
AFTER Conversion ( refer to excel file named: SDP-AC 18 HC-22a )
Recording Time: Start = 08-02-2009 10:14:42, End = 08-02-2009 16:27:30
Average Power (P2): 14.97 kW